Test Case Name
multizone_office_simple_air
Brief Description
The test case represents one floor with five zones of a new construction medium office building in Chicago, IL, USA with total floor area of 1662.66 m2. There are four perimeter zones and one core zone, with each perimeter zone having a window-to-wall ratio of 0.33.
The HVAC system is a single-duct multi-zone VAV system with terminal reheat with one air handler. The air handler cooling coil is served by an air-cooled chiller while the heating coil and terminal box reheat coils are served by an air-to-water heat pump. The embedded controls for the air handler include supply fan static pressure reset and drybulb economizer, while the terminal box controls utilize single-maximum airflow control.
Click here to view detailed documentation.
Available Test Scenarios
Time Periods
peak_heat_day
typical_heat_day
peak_cool_day
typical_cool_day
mix_day
Electricity Prices
constant
dynamic
highly_dynamic
Dependencies
The Modelica model for this test case uses the Modelica Standard Library and the Modelica Buildings Library.
The FMU for this test case is compiled by the open-source JModelica.org.